Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 35 -
11.4 Basic system diagram 4:
1 collector array, 2 storage cylinders (hot water), thermal transfer, auxiliary heating
System 4 has one collector surface, two
storage cylinders, a transfer function and an
auxiliary heating function. The control unit
controls the solar function (temperature
difference regulation, the thermal transfer
(temperature difference regulation,
timeframe) and the auxiliary heating
(thermostat, timeframe). Heat metering is
also possible, e.g. using an impeller flow
meter.
Info Program Manual operation Basic setting
I I I I
Current collector temperature (E1) Timeframe R2 start Pump A1 off/on Code entry
Minimum collector temperature (E1) Timeframe R2 stop A2 off/on Reset/factory setting
Maximum collector temperature (E1) Timeframe R3 start A3 off/on Select basic
configuration
Current storage cylinder temperature
at bottom (E2)
Timeframe R3 stop A4 off/on Maximum collector
temperature
Minimum storage cylinder temperature
at bottom (E2)
Maximum temperature of
storage cylinder
Mode yield metering
Maximum storage cylinder
temperature at bottom (E2)
Solar circuit Td start
Volume flow
Current thermal transfer storage temp.
in middle (E3) for R2 and R3.
Solar circuit Td stop
DFG/WMM
∗∗
Minimum thermal transfer storage
temp. in middle (E3) for R2 and R3.
Start temperature, auxiliary
heating
Glycol type
Minimum thermal transfer storage
temp. in middle (E3) for R2 and R3.
Max temp. of transfer
storage cylinder
Glycol percentage
Current storage temp. at top (E4) R3 Td start Tolerance for solar yield
Minimum storage cylinder temperature
at top (E4)
R3 Td stop Code change
Maximum storage temp. at top (E4) Set time
Flow rate
Daily yield
Total yield
Displayed only if yield metering mode is equivalent to 1 or 2.
∗∗ Displayed only if yield metering mode is equivalent to 2.